Non-Inverter Cooling Only

Daikin's SkyAir is the choice to bring high quality air conditioning to stores and offices like this. Thanks to its many advantages, the SkyAir enjoys an excellent reputation throughout the world wherever it is used.

  • Quiet operation
  • Easy to use
  • Flexible installation
Download Catalogue
Where to buyWhere to buy Compare ProductsCompare Products

Features

Wide Variety of Indoor Units

Daikin meets your needs with full lineup for various types of indoor units (Ceiling mounted cassette type, Ceiling suspended type, Duct connection type and Floor standing type) and power supplies.

Navigation Remote with Simple Operation, Weekly Schedule Timer

Simple, modern designed with fresh white color matches your interior design. Easy to use and smoother operation by following the indications

Quiet operation

Depending on types of indoor units, sound level can range from 32 dB(A) to 45 dB(A). Outdoor unit operation sound is from 48 dB(A) to 58 dB(A). This data is based on “Examples of Sound Levels”, Ministry of the Environment, Japan, November 12, 2002.

Easy Installation and Maintenance

Pre charged for up to 15 m (Applies to RNQ30-48M) 4-direction piping offers greater layout freedom (Applies to RNQ30-48M).

Anti-Corrosion Treatment of Outdoor Heat Exchanger Fins

To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.

Specifications

Ceiling Mounted Cassette (Round Flow) Type

Cassette air conditioner with 360° uniform airflow sets the standard.

  • Avoids uneven temperature and discomfort caused by drafts
  • Comfort enhanced by Round Flow
  • Adapts easily to the installation space
  • Compact body and quiet operation
  • Quick and easy to install
  • Easier to maintain
  • Panel size is same for all models: makes it easy to maintain a neat appearance when multiple, units are installed.
 
13 18 21 26
Model Name Indoor Unit FCNQ13MV1 FCNQ18MV1 FCNQ21MV1 FCNQ26MV1
Outdoor Unit V1 RNQ13MV1 RNQ18MV1 RNQ21MV1 RNQ26MV1
Y1 - - - RNQ26MY1
Cooling Capacity*1,2 kW 3.8 5.3 6.2 7.6
Btu/h 13,000 18,000 21,000 26,000
Power Consumption Cooling*1 kW 1.24 1.89 2.21 2.53
COP [tooltip] W/W 3.07 2.80 2.80 3.00
Indoor Unit Sound Level (H/L)*3 dB(A) 31/28 35/28
Dimensions
(H x W x D)
Unit mm 256 x 840 x 840
Outdoor Unit Sound Level*3 Cooling dB(A) 49 51 52 54
Dimensions (H x W x D) mm 550 x 765 x 285 595 x 845 x 300 735 x 825 x 300
30 36 42 48
Model Name Indoor Unit FCNQ30MV1 FCNQ36MV1 FCNQ42MV1 FCNQ48MV1
Outdoor Unit V1 RNQ30MV1 RNQ36MV1 - -
Y1 RNQ30MY1 RNQ36MY1 RNQ42MY1 RNQ48MY1
Cooling Capacity*1,2 kW 8.8 10.6 12.5 14.1
Btu/h 30,000 36,000 42,600 48,000
Power Consumption Cooling*1 kW 2.73 3.31 4.15 5.04
COP [tooltip] W/W 3.22 3.20 3.01 2.80
Indoor Unit Sound Level (H/L)*3 dB(A) 43/32 44/34 44/36
Dimensions (H x W x D) Unit mm 298 x 840 x 840
Outdoor Unit Sound Level*3 Cooling dB(A) 55 54 56 58
Dimensions (H x W x D) mm 990 x 940 x 320 1,345 x 900 x 320
Note:

*1  Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).

*2  Capacities are net, including a deduction for cooling for indoor fan motor heat. 

*3  Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

 

Ceiling Suspended Type

Upgrade to a quiet and compact system

  • Diffuses comfortable air throughout the room
  • Installation flexibility for freedom of design
  • Quiet operation
  • Easier to maintain
  • Oil resistant grille
 
 
*The indoor unit in this picture is R-410A model.
 
13 18 21 26
Model Name Indoor Unit FHNQ13MV1 FHNQ18MV1 FHNQ21MV1 FHNQ26MV1
Outdoor Unit V1 RNQ13MV1 RNQ18MV1 RNQ21MV1 RNQ26MV1
Y1 - - - RNQ26MY1
Cooling Capacity*1,2 kW 3.8 5.3 6.2 7.6
Btu/h 13,000 18,000 21,000 26,000
Power Consumption Cooling*1 kW 1.58 2.04 2.38 2.65
COP [tooltip] W/W 2.4 2.6 2.6 2.87
Indoor Unit Sound Level (H/L) (220 V)*3 dB(A) 43/39 44/40 45/40
Dimensions (H x W x D) mm 195 x 960 x 680 195 x 1,160 x 680 195 x 1,400 x 680
Outdoor Unit Sound Level*4 Cooling dB(A) 49 51 52 54
Dimensions (H x W x D) mm 550 x 765 x 285 595 x 845 x 300 735 x 825 x 300
30 36 42 48
Model Name Indoor Unit FHNQ30MV1 FHNQ36MV1 FHNQ42MV1 FHNQ48MV1
Outdoor Unit V1 RNQ30MV1 RNQ36MV1 - -
Y1 RNQ30MY1 RNQ36MY1 RNQ42MY1 RNQ48MY1
Cooling Capacity*1,2 kW 8.8 10.4 12.3 14.1
Btu/h 30,000 35,000 42,000 48,000
Power Consumption Cooling*1 kW 3.07 3.64 4.51 5.51
COP [tooltip] W/W 2.87 2.86 2.73 2.56
Indoor Unit Sound Level (H/L) (220 V)*3 dB(A) 45/40 48/42 49/43
Dimensions (H x W x D) mm 195 x 1,400 x 680 195 x 1,590 x 680
Outdoor Unit Sound Level*4 Cooling dB(A) 55 54 56 58
Dimensions (H x W x D) mm 990 x 940 x 320 1,345 x 900 x 320
Note:

*1 Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).

*2 Capacities are net, including a deduction for cooling for indoor fan motor heat.

*3 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

*4 In case of MV1: 220V, MY1: 380V.

 

Duct Connection Low Static Pressure Type

Ideal for quiet, beautiful living space
Suitable for condominiums and apartments, houses and hotels

  • Compact: Small, lightweight, and easy-to-install indoor unit
  • Quiet operation
 

Specifications (R-410A)

9 13 18 21 26
Model Name Indoor Unit FDBNQ09MV1 FDBNQ13MV1 FDBNQ18MV1 FDBNQ21MV1 FDBNQ26MV1
Outdoor Unit V1 RNQ09MV1 RNQ13MV1 RNQ18MV1 RNQ21MV1 RNQ26MV1
Y1 - - - - RNQ26MY1
Cooling Capacity*1,2 kW 2.7 3.8 5.2 6.2 7.6
Btu/h 9,200 13,000 17,700 21,000 26,000
Power Consumption Cooling*1 kW 0.86 1.28 2.06 2.38 2.62
COP [tooltip] W/W 3.14 2.97 2.52 2.6 2.9
Indoor Unit Sound Level (H/L) (220 V)*3 dB(A) 41/38 43/40
Dimensions (H x W x D) mm 260 x 900 x 580 260 x 1,300 x 580
Outdoor Unit Sound Level*3,4 dB(A) 48 49 51 52 54
Dimensions (H x W x D) mm 550 x 765 x 285 595 x 845 x 300 735 x 825 x 300
Note:

*1 Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).

*2 Capacities are net, including a deduction for cooling for indoor fan motor heat.

*3 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

*4 In case of MV1: 220V, MY1: 380V.

 

Duct Connection Middle Static Pressure Type

Unit can be mounted in the ceiling and air can be delivered freely by duct.

  • Freedom of layout: The duct system allows the efficient location of discharge outlets in accordance with the room layout. Duct connection is simpler with standard rear intake chambers.
  • Quiet operation
  • Switchable fan speed: High/Low
  • Drain pipe connection can be done inside the unit. Refrigerant and drain pipe outlets are at the same opening.
 
*The indoor unit in this picture is R-410A model.
 

Specifications (R-410A)

26 30 36 42 48
Model Name Indoor Unit FDMNQ26MV1 FDMNQ30MV1 FDMNQ36MV1 FDMNQ42MV1 FDMNQ48MV1
Outdoor Unit V1 RNQ26MV1 RNQ30MV1 RNQ36MV1 - -
Y1 RNQ26MY1 RNQ30MY1 RNQ36MY1 RNQ42MY1 RNQ48MY1
Cooling Capacity*1,2 kW 7.6 8.8 10.6 12.3 14.1
Btu/h 26,000 30,000 36,000 42,000 48,000
Power Consumption Cooling*1 kW 2.62 3.03 3.53 4.49 5.56
COP [tooltip] W/W 2.90 2.90 3.00 2.74 2.54
Indoor Unit Sound Level (H/L) (220 V)*3 dB(A) 42/38 44/36 45/37 46/37
Dimensions (H x W x D) mm 305 x 1,350 x 680 305 x 1,550 x 680
Outdoor Unit Sound Level*3,4 dB(A) 54 55 54 56 58
Dimensions (H x W x D) mm 735 x 825 x 300 990 x 940 x 320 1,345 x 900 x 320
Note:

*1 Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).

*2 Capacities are net, including a deduction for cooling for indoor fan motor heat.

*3 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

*4 In case of MV1: 220V, MY1: 380V.s

 

An ideal way of space saving with style and functionality, with it’s ease of installation, it is suited to be installed in offices, commercial shops, restaurants, showrooms and mosques.

  • Sleek, stylish and modern to blend into any environment
  • High gloss finishing for easy cleaning
  • Slim profile
  • Stylish black control panel with white LED light for crisp clear display
  • Compact & Easy-to-Use Handset
 
 
  71 100 125 140
Model Name Indoor Unit FVRN71AXV1 FVRN71AXV1 FVRN100AXV1 FVRN125AXV1 FVRN140AXV1
Outdoor Unit RR71CXV1 RR71CXY1 RR100DXY1 RR125DXY1 RR140DXY1
Cooling Capacity kW 8.21 8.21 11.72 13.19 16.12
Btu/h 28000 28000 40000 45000 55000
Power Consumption kW 2840 - 4050 4680 5490
Indoor Unit Sound Pressure Levels dB(A) 44/42/39 44/42/39 49/47/44 50/48/46 54/53/51
Dimensions
(H x W x D)
mm 1850 x 600 x 270 1850 x 600 x 350
Outdoor Unit Sound Pressure Levels dB(A) 58 58 58 60 65
Dimensions
(H x W x D)
mm 753 x 855 x 328 852 x 1030 x 400
Catalog Catalog Where to buyWhere to buy
Back to top